CASE STUDIES

CENTRAL PLANT

 

Northwell Health

New Chiller Plant for Huntington Hospital
Huntington, NY

 

Lizardos prepared contract drawings and supervised the installation of a new roof top chiller plant for Huntington Hospital.  The design provided the installation of four (4) Carrier Aquaforce Chillers, each nominally rated at 410-tons.  The new chillers, each with dual screw compressors, each produce 340-tons of cooling for a 35% propylene glycol solution.  The chillers were rigged onto new dunnage steel by an extension crane. 

 

Included in the design was the reconstruction of the North Penthouse Mechanical Equipment Room with the installation of three (3) new, vertical in-line, chilled water pumps, each rated for 970 gpm at 120-feet TDH.  The pumps are variable speed, with speed control via new variable frequency drives.  The installation included new expansion tank, air separator, glycol makeup tank, associated piping, and new power and control wiring. 

click images for larger view

 